A Revolutionary Counter Shutter that Provides Fire Protection

fire rated counter doors

Key Product Features:

  • Standard Max Width 16’
  • Standard Max Height 9’
  • Max Steel Gauge = 20
  • UL or FM Rated; Conforms to NFPA Standard 80
  • Easily tested and reset
  • Non-tension release

Options & Accessories:

  • Available in Steel (Model 540) or stainless steel (Model 550)
  • SmokeTite UL-Labeled smoke and draft control package.
  • Mounted against face-of-wall or between-jambs for all operation types.
  • Single fusible link cable routing. Available with left-hand or right-hand operation.
  • Fire Door Release System
  • Horns and Strobes
  • Smoke Detectors
  • Vision FireLites
  • Lift Up, Crank or Motor Operation
  • Bottom Bar Sensing Edges
  • Optional Powder Coat Finish

Slat Profile

slat profile
No. 17 Slat Profile

Available:
  22-gauge steel
  22-gauge stainless steel

The FireStar® fire-rated counter shutters meet the demands of applications that require a pleasing appearance combined with certified and labeled fire protection for your property. Our innovative and exclusive design provides lift-up operation that is extremely easy to test and does not require tools to reset the mechanism. As an added bonus, the design offers very quiet and smooth functionality.

FireStar® fire-rated counter shutters are a simple and innovative solution for your safety and fire protection needs. Critical elements necessary in the reliable function of fire doors are incorporated as standard features with FireStars revolutionary design.

These shutters, which are for openings up to 112 square feet, are compact and pleasing in appearance while permitting frequent opening and closing with optimal fire protection.

FireStar® counter shutters have a 3/4, 1 1/2, or 3-hour label rating for masonry or steel jambs (minimum 3/16). Also available in 1 1/2 hour rating for non-masonry walls with 16-gauge steel or wood studs.

Safety

The FireStar® counter shutter can be drop tested easily and reset in a matter of seconds at any time; no tools or service technicians are required. This can be done in addition to the doors required annual inspection by a trained door systems technician. By self-testing throughout the year, facility personnel can be even more confident that their door will function safely in the event of fire.

Reliability

FireStar® counter shutters have been tested and approved to meet the requirements of well known agencies, such as Underwriters Laboratories and Factory Mutual, and conform to NFPA Standard 80.

Approval/Standard Compliances include:

  • Underwriters Laboratories (UL) 10(b) Approval
  • Factory Mutual (FM) Approved Standard 4100 (1990)
  • Designed to comply with governing standard for installation defined in NFPA 80 (2010)

Simplicity

By eliminating one of the fusible link cables, the door and surrounding area look cleaner and less cluttered. It also reduces the risk of cable interference with other nearby fixtures while making installation and drop testing easier.